The product identified with code T00130760 is a Perforated cable tray with slotted bottom, designed for the installation of large quantities of electrical cables while ensuring excellent ventilation and lightness. It is equipped with a safety profile that ensures greater safety during installation and provides high rigidity even with reduced thicknesses. The profile allows for ceiling suspension, using the edge of the channel as an attachment point, and allows the path to be closed with snap-on covers for effective cable protection. It measures 600 mm in width, 75 mm in height and 1,20 mm in thickness, with a standard length of 3000 mm per bar. The cable tray is equipped with side slots for connection to other channels or components, and has twenty-two rows of 25x7 mm slots on the bottom. It is made of Sendzimir galvanised steel, but is also available in stainless steel and with hot-dip galvanised or painted finishes. Identified by the description Perforated cable tray MT.3 75X 600, which summarises its dimensional characteristics, it is certified according to the safety and quality standards required for electrical installations, ensuring reliability and durability over time. When the cover is fitted, it achieves IP20 protection.
| Technical Characteristics | 01,03,11,15,40,41 | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Dimension | |||||||||||
| W (B) | 600 | ||||||||||
| Height | |||||||||||
| H | 75 | ||||||||||
| Thickness | |||||||||||
| [mm] | 1,20 | ||||||||||
| Conductor section | |||||||||||
| [mm2] | 919,20 | ||||||||||
| Weight | |||||||||||
| [Kg/m] | 6,57 | ||||||||||
| Length | |||||||||||
| [mm] | 3000 | ||||||||||
| SWL (N/m) as function of the span (S) [m] -EN 61537 | |||||||||||
| 1,5 m | 1255 | ||||||||||
| 2 m | 706 | ||||||||||
| 2,5 m | 470 | ||||||||||
| 3 m | 141 | ||||||||||
| Usable section of channel [mm²] - EN 50085-2-1 | |||||||||||
| 1,5 m | 43200 | ||||||||||
| 2 m | 43200 | ||||||||||
| 2,5 m | 22500 | ||||||||||
| 3 m | 22000 | ||||||||||
| 3,5 m | 14000 | ||||||||||
| 4 m | 9250 | ||||||||||
| Bottom slots | |||||||||||
| N° | 22 | ||||||||||
| Certified System | |
|---|---|
Norm EN 50085-2-1 Norm EN 61537-1 ed.2007 UL - file E471266 |
|
EN 61537-1
y= Max load (N/m)
x= Distance between supports (m)
D= Uniform load